Certification: | ISO9001 |
---|---|
Shell Material: | Stainless Steel |
Voltage Level: | High Voltage |
Installation: | Fixed |
Structure: | Floorstanding |
Current: | AC |
Suppliers with verified business licenses
GRENO's KYN28 series medium voltage switchgear is an air insulated switchgear with a withdrawable vacuum circuit breaker, with a rated voltage of 10-40.5kv. Mainly used for power transmission of small and medium-sized generators in power plants, distribution of power to factories and mining enterprises, and receiving and transmitting power to power system substations, as well as starting large high-voltage motors, to control, protect, and monitor the system. In addition to being compatible with domestic VS1 vacuum circuit breakers, it can also be used in conjunction with ABB's VD4, Siemens' domestic ZN65A's 3AH5, GE's VB2, etc. It is a high-performance distribution device.
No. |
Description |
Requirement |
1 |
Ambient air temperature |
-10ºC ~ +40ºC |
2 |
Daily average saturated vapor pressure |
≤ 2.2×10mpa |
3 |
Monthly average saturated vapor pressure |
≤ 1.8×10mpa |
4 |
Daily average relative humidity |
≤95% |
5 |
Monthly average relative humidity |
≤90% |
6 |
Altitude |
≤1000m |
7 |
Anti-seismic intensity |
≤ 8° |
7 |
No fire, explosion, danger, severe contamination, chemical corrosion and violent vibration. |
Techincal Satisfaction1
item |
Unit |
Parameters |
|||
rated voltage |
KV |
7.2 /12 |
|||
rated current |
HZ |
50 |
|||
rated current of circuit breaker |
A |
630\2000 |
|||
rated current of switch cabinet |
A |
630\2000 |
|||
rated current of dynamic stability (4S) |
KA |
16\20\25\31.5\40\50 |
|||
rated current of dynamic stability (peak) |
KA |
40\50\63\80\100\125 |
|||
rated short circuit drop-out current |
KA |
16\20\25\31.5\40\50 |
|||
rated short circuit making current (peak) |
KA |
40\50\63\80\100\125 |
|||
Rated insulation level |
1min power frequency withstand voltage |
KA |
24 |
32 |
42 |
lighting impulse withstand voltage |
KA |
40 |
60 |
75 |
|
protection degree |
IP2X shell: IP4X, it is IP2X when compartment and circuit breaker room is open |
Techincal Satisfaction2
Serial No. |
Item |
Unit |
Technical parameters |
||||
1 |
Rated voltage |
KV |
24 |
||||
2 |
Rated frequency |
HZ |
50/60 |
||||
3 |
Rated insulation level |
1 min withstand voltage (effective value) |
KV |
Phase to phase & phase to earth |
60 |
Isolation fracture |
79 |
Lighting impulse withstand voltage (peak value) |
125 |
145 |
|||||
Auxiliary control circuit power frequency withstand voltage |
V |
2000 |
|||||
4 |
Rated current |
A |
630,1250,1600,2000,2500,3150 |
||||
5 |
Specified short-circuit dropout current |
KA |
20, 25, 31.5 |
||||
6 |
Rated short-circuit making current (peak value) |
KA |
50, 63, 80 |
||||
7 |
Rated short time withstand current (4S) |
KA |
20, 25, 31.5 |
||||
8 |
Rated peak withstand current |
KA |
50, 63, 80 |
||||
9 |
Auxiliary control circuit rated voltage |
V |
AC or DC 110/220 |
||||
10 |
Protection level |
V |
IP4X (the circuit breaker chamber door is open or isolation chamber is IP2X) |
||||
11 |
Outline dimension |
mm |
1000*1910*24001 |
||||
12 |
Weight |
Kg |
840-1500 |
Suppliers with verified business licenses