Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | High-Speed Circuit Breaker |
Arc-extinguishing Medium: | SF6 |
Installation: | Fixed |
Poles Number: | 3 |
Suppliers with verified business licenses
Designed by GRENO (XIAMEN) SWITCHGEAR CO., LTD., SF6 load break switches are ideal for switching circuits with currents up to 630 A in 6 kV, 10 kV, and 20 kV/24kV/50 Hz three-phase AC networks.
Insulation Ability: The switchgear has an increased insulation ability for arc-extinguishing when in the open status, thanks to the SF6 gas filled with a pressure of 0.03Mpa~0.04Mpa.
Compact Size: The switchgear is designed to be smaller in size, ensuring safe and efficient operation.
Best Material: The switchgear's copper contactor is made of T2 copper, which contains more than 99.95% Cu content. The special production process guarantees excellent abrasion rigidity.
Increased Phased Distance: The switchgear features a phased distance of 210mm, with a particular design that lengthens the air and creepage distance for enhanced performance.
We pay meticulous attention to every detail in the design and production of our Switchgear Component SC6. Trust GRENO (XIAMEN) SWITCHGEAR CO., LTD. for reliable and high-quality switchgear components.
Item NO. | Name | Unit | Technical parameters | |||
Load break switch panel | ||||||
1 | Rated Voltage Un | kV | 12 | 24 | 36 | |
2 | Rated Frequency | Hz | 50 | 50 | 50 | |
3 | Rated Current | A | 630 | 630 | 630 | |
4 | Rated Load Breaking Current | A | 630 | 630 | 630 | |
5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | 20 | |
6 | Rated Short Time Duration | s | 3 | 3 | 3 | |
7 | Rated Peak Withstand Current | kA | 50 | 50 | 50 | |
8 | Rated Closed Switch - Off Current | A | 630 | 630 | 630 | |
9 | Rated Cable Charging Breaking Current | A | 10 | 10 | 10 | |
10 | Rated Active Load Breaking Current | A | 630 | 630 | 630 | |
13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | 20 | |
14 | Rated Short-Circuit Current Making Times | times | 2 | 2 | 2 | |
15 | Rated Current Breaking Times | times | 10 | 10 | 10 | |
16 | Mechanical Endurance | Load Break Switch | times | 3000 | 3000 | 3000 |
Earthing Switch | times | 2000 | 2000 | 2000 | ||
17 | SF6 gas anual leakage rate≤ | /year | 0.10% | 0.10% | 0.10% | |
18 | Rated Insulation Level | Unit | Technical parameters | |||
1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 48 | 60 | 110 | |
Phase to Phase | kV | 42 | 50 | 85 | ||
Phase to Earth | kV | 42 | 50 | 85 | ||
Lightning impulse withstand voltage(peak) | On isolating distance | kV | 85 | 145 | 215 | |
Phase to Phase | kV | 75 | 125 | 185 | ||
Phase to Earth | kV | 75 | 125 | 185 |
We offer a 12-month warranty for all our products, with the possibility of extending it further (negotiable). Our team provides type testing, technical support, and marketing assistance to ensure your satisfaction. We also welcome customized designs to meet your specific requirements. Additionally, we offer reliable after-sales service to address any concerns you may have.