Breaking Capacity: | High Voltage Circuit Breakers |
---|---|
Operation: | Electric Type |
Speed: | High-Speed Circuit Breaker |
Arc-extinguishing Medium: | SF6 |
Installation: | Fixed |
Structure: | Lbs |
Suppliers with verified business licenses
With their robust design and high-quality construction, our SF6 load break switches ensure optimal performance and longevity. They are specifically engineered to handle high currents, making them suitable for a wide range of applications.
Featuring advanced technology, our load break switches provide seamless switching operations, allowing for smooth and uninterrupted power flow. This ensures the safety and stability of your electrical circuits.
Trust GRENO (XIAMEN) SWITCHGEAR CO., LTD. for all your load break switch needs.
Item NO. | Name | Unit | Technical parameters | |||
Load break switch panel | ||||||
1 | Rated Voltage Un | kV | 12 | 24 | 36 | |
2 | Rated Frequency | Hz | 50 | 50 | 50 | |
3 | Rated Current | A | 630 | 630 | 630 | |
4 | Rated Load Breaking Current | A | 630 | 630 | 630 | |
5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | 20 | |
6 | Rated Short Time Duration | s | 3 | 3 | 3 | |
7 | Rated Peak Withstand Current | kA | 50 | 50 | 50 | |
8 | Rated Closed Switch - Off Current | A | 630 | 630 | 630 | |
9 | Rated Cable Charging Breaking Current | A | 10 | 10 | 10 | |
10 | Rated Active Load Breaking Current | A | 630 | 630 | 630 | |
13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | 20 | |
14 | Rated Short-Circuit Current Making Times | times | 2 | 2 | 2 | |
15 | Rated Current Breaking Times | times | 10 | 10 | 10 | |
16 | Mechanical Endurance | Load Break Switch | times | 3000 | 3000 | 3000 |
Earthing Switch | times | 2000 | 2000 | 2000 | ||
17 | SF6 gas anual leakage rate≤ | /year | 0.10% | 0.10% | 0.10% | |
18 | Rated Insulation Level | Unit | Technical parameters | |||
1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 48 | 60 | 110 | |
Phase to Phase | kV | 42 | 50 | 85 | ||
Phase to Earth | kV | 42 | 50 | 85 | ||
Lightning impulse withstand voltage(peak) | On isolating distance | kV | 85 | 145 | 215 | |
Phase to Phase | kV | 75 | 125 | 185 | ||
Phase to Earth | kV | 75 | 125 | 185 |
Our latest switchgear with enhanced features and benefits:
The insulation ability for arc-extinguishing is significantly improved when the switchgear is in an open status. This is achieved by filling the switchgear with SF6 gas at a pressure range of 0.03Mpa~0.04Mpa.
We have designed our switchgear to be smaller in size without compromising on safety. By utilizing advanced techniques, we have successfully made the whole size of the switchgear smaller, making it easier to install and handle.
Our switchgear features a copper contactor with over 99.95% Cu content. This special production process ensures the contactor's excellent abrasion rigidity. We proudly call this material T2 copper.
In order to enhance safety, we have designed our switchgear with a phased distance of 210mm. This particular design extends the air and creepage distance, minimizing the risk of electrical accidents.
Suppliers with verified business licenses