Type: | Switch Cabinet |
---|---|
Max. Current: | 630A |
Max. Voltage: | 12kv |
Withstand Current: | 20ka,16ka |
Rated Voltage: | 12kv |
Load Breaking Current: | 630A |
Samples: |
---|
Suppliers with verified business licenses
GRENO (XIAMEN) SWITCHGEAR CO., LTD. offers high-quality SF6 load break switches that are specifically designed for switching circuits with currents up to 630 A in 6 kV, 10 kV, and 20 kV / 24kV / 50 Hz three-phase A.C. networks.
Choose GRENO (XIAMEN) SWITCHGEAR CO., LTD.'s SF6 load break switches for efficient and reliable switching in your electrical circuits. Upgrade your equipment today!
Introducing our latest switchgear with enhanced features and benefits:
The insulation ability for arc-extinguishing is significantly improved when the switchgear is in an open status. This is achieved by filling the switchgear with SF6 gas at a pressure range of 0.03Mpa~0.04Mpa.
We have designed our switchgear to be smaller in size without compromising on safety. By utilizing advanced techniques, we have successfully made the whole size of the switchgear smaller, making it easier to install and handle.
Our switchgear features a copper contactor with over 99.95% Cu content. This special production process ensures the contactor's excellent abrasion rigidity. We proudly call this material T2 copper.
In order to enhance safety, we have designed our switchgear with a phased distance of 210mm. This particular design extends the air and creepage distance, minimizing the risk of electrical accidents.
Choose GRENO (XIAMEN) SWITCHGEAR CO., LTD. for reliable and efficient switchgear solutions that meet the highest standards of quality and safety.
We strictly control the quality of our products by selecting the best quality epoxy resin, even though it may be expensive. Before every production, we make a belt transect with epoxy resin to ensure its quality. According to test data, we have successfully controlled the major material qualities such as bending strength, tensile strength, and impact strength.
Our internal contact terminals are made of permanent magnetism material, ensuring reliable performance. When the LBS switches to the open position, the arc naturally becomes thinner and thinner, leading to self-extinguishment in SF6 gas.
We warmly welcome any enquiries at any time. Feel free to send us your questions or requests, and we will be happy to assist you.
Item NO. | Name | Unit | Technical parameters | |||
Load break switch panel | ||||||
1 | Rated Voltage Un | kV | 12 | 24 | 36 | |
2 | Rated Frequency | Hz | 50 | 50 | 50 | |
3 | Rated Current | A | 630 | 630 | 630 | |
4 | Rated Load Breaking Current | A | 630 | 630 | 630 | |
5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | 20 | |
6 | Rated Short Time Duration | s | 3 | 3 | 3 | |
7 | Rated Peak Withstand Current | kA | 50 | 50 | 50 | |
8 | Rated Closed Switch - Off Current | A | 630 | 630 | 630 | |
9 | Rated Cable Charging Breaking Current | A | 10 | 10 | 10 | |
10 | Rated Active Load Breaking Current | A | 630 | 630 | 630 | |
13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | 20 | |
14 | Rated Short-Circuit Current Making Times | times | 2 | 2 | 2 | |
15 | Rated Current Breaking Times | times | 10 | 10 | 10 | |
16 | Mechanical Endurance | Load Break Switch | times | 3000 | 3000 | 3000 |
Earthing Switch | times | 2000 | 2000 | 2000 | ||
17 | SF6 gas anual leakage rate≤ | /year | 0.10% | 0.10% | 0.10% | |
18 | Rated Insulation Level | Unit | Technical parameters | |||
1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 48 | 60 | 110 | |
Phase to Phase | kV | 42 | 50 | 85 | ||
Phase to Earth | kV | 42 | 50 | 85 | ||
Lightning impulse withstand voltage(peak) | On isolating distance | kV | 85 | 145 | 215 | |
Phase to Phase | kV | 75 | 125 | 185 | ||
Phase to Earth | kV | 75 | 125 | 185 |
Our Services
Suppliers with verified business licenses