Certification: | ISO9001 |
---|---|
Shell Material: | Steel Plate |
Voltage Level: | Medium Voltage |
Installation: | Fixed |
Structure: | Floorstanding |
Current: | AC |
Suppliers with verified business licenses
C - Cable switch module | F - Cable switch module | V - Cable switch module |
D - Direct cable connection module | De - Direct cable connection module with earthing switch | M - Metering module |
Project |
Cable feeder |
Transformer feeder |
Breaker V unit |
Rated voltage |
12/24 |
12/24 |
12/24 |
Rated frequency |
50 or 60 |
50 or 60 |
50 or 60 |
Rated insulation level |
|||
Power frequency withstand voltage |
50/60 |
50/60 |
50/60 |
Lightning impulse withstand voltage |
125/145 |
125/145 |
125/145 |
Rated current |
630 |
≤125 Note1 |
630 |
Breaking closing ability |
|||
Rated active load breaking current |
630 |
|
630 |
Active load breaking current |
31.5 |
|
31.5 |
Rated cable charging breaking current |
10 |
|
10 |
Rated breaking current transfer |
|
2700 |
|
Rated short-circuit breaking current |
|
Note2 |
20 |
Rated short-circuit current |
50 |
|
50 |
Dynamic thermal stability capabilities |
|||
Rated short time withstand current |
20 |
|
20 |
Rated short duration |
3 |
|
3 |
Rated peak withstand current |
50 |
|
50 |
Mechanical life Times |
3000 |
3000 |
3000 |
Other |
|||
Ambient temperature ºC |
-40 ~ +60 |
-40 ~ +60 |
-40 ~ +60 |
Gas pressure...ºC when the gauge... |
0.03 |
0.03 |
0.03 |
Degree of protection |
IP67 Gas tank IP67 |