Introducing the GSC-36, an indoor high-voltage SF6 load switch designed for power supply and transformer substations. With a rated voltage of 36kV/40.5kV and SF6 gas as an arc-extinguishing and insulation medium, this switchgear offers exceptional performance and reliability.
The GSC-36 load switch is compliant with the standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420, ensuring its quality and performance.
No |
Item |
Unit |
Parameter |
1 |
Rated voltage |
kV |
36 |
2 |
Rated frequency |
Hz |
50/60 |
3 |
Rated current |
A |
630 |
4 |
wet 1min Power frequency withstand voltage dry |
kV
kV |
95
110 |
5 |
Lightning impulse withstand voltage |
kV |
185/215 |
6 |
Rated short circuit breaking current (peak) |
kA |
50 |
7 |
Rated activeload and close circuit breaking current |
A |
50 |
8 |
Rated transferring current |
A |
1000 |
9 |
Rated short circuit making current (peak) |
kA |
50 |
10 |
Rated cable(line) charging breaking current |
A |
50 and 10 |
11 |
Cable charge breaking current in earthing fault |
A |
20 |
12 |
Rated withstand current (peak) |
kA |
50 |
13 |
Short time withstand current (2s) |
kA |
20 |
14 |
Mechanism life |
times |
200 |
Suppliers with verified business licenses