Certification: | CCC, ISO9001 |
---|---|
Shell Material: | Stainless Steel |
Voltage Level: | Medium Voltage |
Installation: | Removable |
Structure: | Floorstanding |
Current: | AC |
Suppliers with verified business licenses
Item |
Unit |
Parameters |
||
Rated voltage |
KV |
12 |
24 |
|
Rated frequency |
Hz |
50 |
||
Rated current |
A |
630/1250 |
||
Rated load breaking current |
A |
630 |
||
Rated short time withstand current (effective value) |
A |
20/31.5 |
||
Rated short circuit duration |
S |
3 |
||
Rated short circuit making current |
KA |
50 |
||
Rated peak withstand current |
KA |
50 |
||
Rated cable charging breaking current |
A |
10 |
||
Rated active load and close circuit breaking current |
A |
630 |
||
MAX transfer current |
A |
1750 |
||
Earthing switch short time withstand current (2s) |
KA |
17.4/20 |
||
Rated current breaking times |
Times |
≥10 |
||
Load break switch mechanical life |
Times |
≥5000 |
||
Earthing switch mechanical life |
Times |
≥2000 |
||
1 min power frequency withstand voltage |
Common value |
KV |
42 |
55 |
Across insulate distance |
KV |
48 |
65 |
|
Lightning impulse withstand voltage |
Common value |
KV |
75 |
125/150 |
Across insulate distance |
KV |
85 |
150/160 |
|
Operating mechanism |
|
Manual or motor |
||
Operating voltage |
V |
AC/DC 220/110, DC48/24 |
||
Protection degree |
|
IP3X |
Item NO. | Name | Unit | Technical parameters | |||
GRM-C | GRM-F | GRM-V | ||||
1 | Rated Voltage Un | kV | 24 | 24 | ||
2 | Rated Frequency | Hz | 50 | 50 | ||
3 | Rated Current | A | 630 | 125 | 630 | |
4 | Rated Load Breaking Current | A | 630 | 125 | ||
5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | ||
6 | Rated Short Time Duration | s | 3 | 3 | ||
7 | Rated Peak Withstand Current | kA | 50 | 50 | ||
8 | Rated Closed Switch - Off Current | A | 630 | |||
9 | Rated Cable Charging Breaking Current | A | 10 | 25 | ||
10 | Rated Active Load Breaking Current | A | 630 | |||
11 | Max. Transfer Current | A | 1750 | |||
12 | Expected Fuse Short-Circuit Breaking Current(rms) | kA | 50 | |||
13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | ||
14 | Rated Short-Circuit Current Making Times | Times | 2 | |||
15 | Rated Current Breaking Times | Times | 10 | |||
16 | Mechanical Endurance | Load Break Switch | Times | 5000 | ||
Earthing Switch | Times | 2000 | 2000 | |||
Disconnector | Times | 3000 | ||||
Circuit Breaker | Times | 10000 | ||||
17 | SF6 gas anual leakage rate | ≤1%/Y | ||||
18 | Rated Insulation Level | Unit | Technical parameters | |||
1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 60 | |||
Phase to Phase | kV | 50 | ||||
Phase to Earth | kV | 50 | ||||
Lightning impulse withstand voltage(peak) | On isolating distance | kV | 145 | |||
Phase to Phase | kV | 125 | ||||
Phase to Earth | kV | 125 | ||||
21 | optional :Motorised Operating Mechanism- voltage | V | DC24,DC48,DC110,DC220,AC220 |
Suppliers with verified business licenses