Breaking Capacity: High Voltage Circuit Breakers
Operation: Manual or Motorized
Speed: High-Speed Circuit Breaker
Arc-extinguishing Medium: SF6
Installation: Fixed
Structure: Lbs
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Fujian, China
to see all verified strength labels (22)

Basic Info.

Model NO.
GSC
Poles Number
3
Type
Load Break Switch
Function
Load Break Switch
Certification
ISO9001-2000, Type Test Report
Transport Package
Wooden Case
Origin
Xiamen
Production Capacity
5000pieces Per Month

Product Description

Product Description

24kv/630A-20ka Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs) Phase Distrance 210mm or 230mm
24kv/630A-20ka Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs) Phase Distrance 210mm or 230mm
24kv/630A-20ka Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs) Phase Distrance 210mm or 230mm


24kv/630A-20ka Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs) Phase Distrance 210mm or 230mm

++++General
GSC is an indoor high-voltage SF6 load break switch, for switchgear with the rated voltage of 12kV/24kV, adopted  SF6 gas as arc-extinguishing and insulation medium, including the three contactors for switching-on and switching-off and to-ground, and is characteristic in its small volume, its convenient installation and operation and its the great adaptability with surroundings.
GSC is an indoor high-voltage SF6 load switch and GSC-SQC SF6 load switch plus fuse combination can function to protect and control the electric equipments for power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation.
Complied with the standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc..
24kv/630A-20ka Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs) Phase Distrance 210mm or 230mm

++++Service environment
a) Air temperature
Maximum temperature: +40ºC; Minimum temperature:-35ºC
b) Humidity
Monthly average humidity 95%; Daily average humidity 90% .
c) Altitude above sea level
Maximum installation altitude: 2500m
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc.
e) No frequent violent shake

++++ Main technical specifications

24kv/630A-20ka Indoor Rmu Use Sf6 Switch Disconnector Load Break Switch (lbs) Phase Distrance 210mm or 230mm
No Item Unit Parameter
1 Rated voltage kV 12 24
2 Rated frequency Hz 50/60
3 Rated current A 630/800
4 1min Power frequency
withstand voltage
wet kV 38 50
dry kV 48 60
5 Lightning impulse withstand voltage kV 75 125/150
6 Rated short circuit breaking current (peak) kA 80 63
7 Rated active load and close circuit breaking current A 63 50
8 Rated transferring current A 1700 1200
9 Rated short circuit making current (peak) kA 80 63
10 Rated cable(line) charging breaking current A 50 and 10
11 Cable charge breaking current in earthing fault A 20 20
12 Rated withstand current (peak) kA 80 63
13 Short time withstand current (2s) kA 31.5 25
14 Mechanism life times 5000 2000

Note: For short circuit breaking and peak current is based on Fuse plus combination. 
++++Installation, Maintenance & Service.

++++Installation, Adjustment

GSC type load break switch has been strictly tested before delivering from the factory, and fully meet the technical standards, must carefully read the installation manual and prepare as below before the installation and adjustment.
Check the external appearance, any damage product is not allowed to use.
Clean the equipment and get rid of the dust and dirt may cause by the transportation or other causes.

Keep the external appearance away from dust, dirt and damp.

++++Matters need attention
It is NOT allowed to disassembly the self-sealed valve in front of switch( connecting end of meter).
It is NOT allowed to unload the seal screws on switch at any time.

+++Packaging & Shipping +

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2018

Suppliers with verified business licenses

Manufacturer/Factory & Trading Company
Number of Employees
54
Year of Establishment
2010-08-11