GSC-24 Indoor load circuit breaker, rated voltage 12KV, using SF6 gas fire extinguishing and insulation medium. It includes three contactors for opening and closing.
The distance between phases can be 200mm, 210mm, or 230mm.
It can protect and control the electrical equipment of power supply and substations, especially suitable for ring main unit, cable branch cabinets, and distribution switchgear.
Environmental Condition
This load disconnect switch can be used in high-altitude areas.
Environmental temperature: -40 º C~+40 º C
Relative humidity: daily average ≤ 95%, monthly average ≤ 90%
Altitude: ≤ 2000 specification m
Earthquake intensity: ≤ 8 degrees
No corrosive gases, no flammable gases, no vapors or vapors.
The resin cast has anti-explosion pressure relief value fitted at back for ensuring safety of operators
GSC-24 has single K-type spring mechanisms, normally used for incoming and outgoing line.
GSC-24 has double A-type spring mechanisms, normally used together with fuse for transformer protection.
Build-in capacitive sensors
Optional motor operation
Operation GAS pressure meter or testing points
Company Information
With the advanced technology support from our UK partner,with rich industrial and exporting experience,GRENO is focused on producing a fully range of power distribution and protection products
For many years,we've been exporting to many countries in Asia,Europe, Middle East,America and Africa, Our products were mainly exported to Europe and our quality has won their deep trust and very good comments.
Main Technical Data
Item NO. | Name | Unit | Technical parameters | |||
Load break switch panel | ||||||
1 | Rated Voltage Un | kV | 12 | 24 | 36 | |
2 | Rated Frequency | Hz | 50 | 50 | 50 | |
3 | Rated Current | A | 630 | 630 | 630 | |
4 | Rated Load Breaking Current | A | 630 | 630 | 630 | |
5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | 20 | |
6 | Rated Short Time Duration | s | 3 | 3 | 3 | |
7 | Rated Peak Withstand Current | kA | 50 | 50 | 50 | |
8 | Rated Closed Switch - Off Current | A | 630 | 630 | 630 | |
9 | Rated Cable Charging Breaking Current | A | 10 | 10 | 10 | |
10 | Rated Active Load Breaking Current | A | 630 | 630 | 630 | |
13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | 20 | |
14 | Rated Short-Circuit Current Making Times | times | 2 | 2 | 2 | |
15 | Rated Current Breaking Times | times | 10 | 10 | 10 | |
16 | Mechanical Endurance | Load Break Switch | times | 3000 | 3000 | 3000 |
Earthing Switch | times | 2000 | 2000 | 2000 | ||
17 | SF6 gas anual leakage rate≤ | /year | 0.10% | 0.10% | 0.10% | |
18 | Rated Insulation Level | Unit | Technical parameters | |||
1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 48 | 60 | 110 | |
Phase to Phase | kV | 42 | 50 | 85 | ||
Phase to Earth | kV | 42 | 50 | 85 | ||
Lightning impulse withstand voltage(peak) | On isolating distance | kV | 85 | 145 | 215 | |
Phase to Phase | kV | 75 | 125 | 185 | ||
Phase to Earth | kV | 75 | 125 | 185 |