Type: | Switch Cabinet |
---|---|
Max. Current: | 630A |
Max. Voltage: | 12kv |
Withstand Current: | 20ka,16ka |
Rated Voltage: | 12kv |
Load Breaking Current: | 630A |
Samples: |
---|
Suppliers with verified business licenses
Designed by GRENO (XIAMEN) SWITCHGEAR CO., LTD., our SF6 load break switches are perfect for switching circuits with currents up to 630 A in 6 kV, 10 kV, and 20 kV/24kV/50 Hz three-phase A.C. networks.
Upgrade your electrical systems with GRENO (XIAMEN) SWITCHGEAR CO., LTD.'s reliable and efficient switchgear. Experience enhanced insulation, compact design, premium materials, and optimized performance. Trust in our expertise to meet your electrical needs.
5) We strictly control the quality of our products by choosing the best quality epoxy resin, despite its higher cost. Before every production, we conduct a belt transect test using epoxy resin to ensure its quality.
Based on the test data, we have effectively controlled the quality of major materials, such as bending strength, tensile strength, and impact strength.
6) Our internal contact terminals are made of permanent magnetism material. When the LBS switches to the open position, the arc naturally becomes thinner and eventually extinguishes in SF6 gas.
We warmly welcome any inquiries at any time. Please feel free to contact us.
Item NO. | Name | Unit | Technical parameters | |||
Load break switch panel | ||||||
1 | Rated Voltage Un | kV | 12 | 24 | 36 | |
2 | Rated Frequency | Hz | 50 | 50 | 50 | |
3 | Rated Current | A | 630 | 630 | 630 | |
4 | Rated Load Breaking Current | A | 630 | 630 | 630 | |
5 | Rated Short Time Withstand Current(rms) | kA | 20 | 20 | 20 | |
6 | Rated Short Time Duration | s | 3 | 3 | 3 | |
7 | Rated Peak Withstand Current | kA | 50 | 50 | 50 | |
8 | Rated Closed Switch - Off Current | A | 630 | 630 | 630 | |
9 | Rated Cable Charging Breaking Current | A | 10 | 10 | 10 | |
10 | Rated Active Load Breaking Current | A | 630 | 630 | 630 | |
13 | Earthing Switch 2s Short Time Withstand Current | kA | 20 | 20 | 20 | |
14 | Rated Short-Circuit Current Making Times | times | 2 | 2 | 2 | |
15 | Rated Current Breaking Times | times | 10 | 10 | 10 | |
16 | Mechanical Endurance | Load Break Switch | times | 3000 | 3000 | 3000 |
Earthing Switch | times | 2000 | 2000 | 2000 | ||
17 | SF6 gas anual leakage rate≤ | /year | 0.10% | 0.10% | 0.10% | |
18 | Rated Insulation Level | Unit | Technical parameters | |||
1min Power Frequency withstand voltage(rms) | On isolating distance | kV | 48 | 60 | 110 | |
Phase to Phase | kV | 42 | 50 | 85 | ||
Phase to Earth | kV | 42 | 50 | 85 | ||
Lightning impulse withstand voltage(peak) | On isolating distance | kV | 85 | 145 | 215 | |
Phase to Phase | kV | 75 | 125 | 185 | ||
Phase to Earth | kV | 75 | 125 | 185 |